Wiring of the standard device
Standard devices in the power range 0.37 ... 11 kW
Motor connection
5
5.4
5.4.6
5.4−10
EDSVS9332P EN 5.0−07/2013
PE PE
UUVVWW
T1 T1T2 T2
U, V, W
T1, T2
0.5...0.6 Nm
4.4...5.3 lb-in
U, V, W
T1, T2
0.5...0.6 Nm
4.4...5.3 lb-in
2233
1
1
00
9300std011
Fig. 5.4−6 Motor connection with PTC thermistor or thermal contact (NC contact)
Motor connection with Lenze system cable with integrated control
cable for the motor temperature monitoring
Shield sheet
Clamp entire shield and shield of the control cable for the motor
temperature monitoring with the straps. If required, fix by means of
cable tie.
Motor cable connection and separate control cable for the motor
temperature monitoring
Shield sheet
Clamp shield of the motor cable and shield of the cable for the motor
temperature monitoring with the straps. If required, fix by means of
cable tie.
U, V, W
Motor cable connection
Check the correct polarity. Observe maximum length of the motor cable. Use
wire end ferrules for flexible cables.
Max. connectable cable cross−section: 4 mm
2
, with pin−end connector
> 4 mm
2
T1, T2 for motor temperature monitoring
Cable connection for PTC thermistors or thermal contacts (NC contacts)