Configuration
Overview of monitoring functions
8
8.3
8.32
EDSVS9332P EN 5.0−07/2013
Possible fault responses
l Lenze setting
ü Can be set
Monitoring
OffFail−QSPWarningMessageTRIPCode
SourceDescriptionFault message
0015 OC5 Device utilisation I x t (fix 100%) MCTRL l
0016 OC6 I
2
x t overload MCTRL l
0018 OC8 I
2
x t overload advance warning MCTRL C0606 ü l ü
x032 LP1 Failure of a motor phase
(current limit adjustable under C0599)
Caution: Can only be used with asynchronous motors. The
function block MLP1 must be entered in C0465.
MCTRL C0597 ü ü l
x082 Sd2 Resolver error at X7
Note: If monitoring is switched off or in the case of "Warning",
the machine can reach very high speeds in the case of fault,
which may result in the damage of the motor and the machine
that is driven!
MCTRL C0586 l ü ü
x083 Sd3 Interruption of the digital frequency coupling. The input signal
˜Lamp Control˜ at X9/8 is LOW
Please note: In the case of "Warning" (C0587 = 2), the drive can
be destroyed if the fault is not eliminated in time!
MCTRL C0587 l ü ü
x085 Sd5 At analog input X6/1, X6/2, the input current is < 2 mA
Monitoring only possible if C0034 = 1
MCTRL C0598 ü ü l
x087 Sd7 Absolute value encoder error at X8 MCTRL ü l
x088 Sd8 SinCos encoder error at X8
(filter setting under C0575)
MCTRL C0580 ü l
Speed
x190 nErr Speed control error
(speed window can be set in C0576)
MCTRL C0579 ü ü ü ü l
x200 NMAX Maximum speed (C0596) has been exceeded. MCTRL l
Time−out / overflow
0105 H05 Internal fault (memory) Internal l
x153 P03 Following error (digital frequency > C0255) Internal C0589 ü l ü
x163 P13 Angle controller overflow Internal C0590 l ü ü
x169 P19 Input signal at X9 is limited Internal C1292 ü l ü
Parameter setting
0072 PR1 Check sum error in parameter set 1 Internal l
0074 PEr Program error Internal l
0075 PR0 Error in the parameter sets Internal l
0079 PI Error during parameter initialisation Internal l
x089 PL Error during rotor position adjustment Internal l
Positioning