Configuration
Basic configurations
8
8.5
8.5−12
EDSVS9332P EN 5.0−07/2013
IMPORTANTPossible settingsCode
SelectionLenzeDesignationNo.
C0183 DIAGNOSTICS )
Drive diagnostics
l Indicates fault or status
information
l Shows the smallest
numerical value if several
pieces of fault or status
information are pending at
the same time
0 OK No fault
101 Initialisation Initialisation phase
102 TRIP/fault TRIP active
103 Emergency stop Emergency stop was carried out
104 IMP message Message active
105 Power OFF
Function is not supported
111 BSP C135 operation inhibit
Operation inhibit
112 BSP AIF operation inhibit
113 BSP CAN operation inhibit
121 RSP terminal 28 controller inhibit Controller inhibited through
X5/28
122 Controller inhibit, internal 1 DCTRL−CINH1
123 Controller inhibit, internal 2 DCTRL−CINH2
124 RSP C135/STOP controller inhibit STOP key on the keypad
125 RSP AIF controller inhibit Controller inhibited via AIF
126 RSP CAN controller inhibit Controller inhibited through
CAN
141 Switch−on inhibit Restart protection active
142 IMP inhibit pulse inhibit High resistance power outputs
151 QSP terminal ext. quick stop Quick stop via MCTRL−QSP
152 QSP−C135 quick stop Quick stop via STOP key on the
keypad
153 QSP−AIF quick stop Quick stop via AIF
154 QSP−CAN quick stop Quick stop via system bus
250 Warning C168 Warning active
C0190 NSET ARIT 0 0
1
2
3
4
5
OUT = C46
C46 + C49
C46 − C49
C46 * C49
C46 / C49
C46/(100 − C49)
NSET
Arithmetic block in the NSET
function block
l Connects main setpoint
C0046 and additional
setpoint C0040
See system
manual
(extension)
C0195 BRK1 T ACT 99.9 0.0 {0.1 s} 99.9 BRK1
Brake closing time.
Engagement time of the
mechanical holding brake
l After the time under C0195
has elapsed, the
"mechanical brake closed"
status is reached
See system
manual
(extension)