Wiring of the standard device
Standard devices in the power range 0.37 ... 11 kW
Mains connection, DC supply
5
5.4
5.4.3
5.4−4
EDSVS9332P EN 5.0−07/2013
5.4.3 Mains connection, DC supply
Note!
ƒ If a mains filter or RFI filter is used and the cable length
between mains/RFI filter and drive controller exceeds
300 mm, install a shielded cable.
ƒ For DC−bus operation or DC supply, we recommend using
shielded DC cables.
Stop!
ƒ To avoid damaging the PE stud, always install the shield sheet
and the PE connection in the order displayed. The required
parts are included in the accessory kit.
ƒ Do not use lugs as strain relief.
M6
M5
2
3
4
5
6
7
1
0
L1 L2 L3
+UG -UG
PE
a
1.7 Nm
15 lb-in
PE
M5
3.4Nm
30 lb-in
a
}
+
PE
4
2
8
0
7
9300vec130
Fig. 5.4−2 Installation of shield sheet for drive controllers 0.37 ... 11 kW
PE stud
Screw on M5 nut and tighten hand−tight
Slide on fixing bracket for shield sheet
Slide on serrated lock washer
Slide on PE cable with ring cable lug
Slide on washer
Slide on spring washer
Screw on M5 nut and tighten it
Screw shield sheet on fixing bracket with two M4 screws (a)
Shield sheet installation