EDS84DMOTCAN EN 3.0 - 11/2011 L 97
Communication manual 8400 motec CANopen
Implemented CANopen objects
I-1201 - SDO2 server parameter
Setting of the identifiers for SDO server channel 2.
The server SDO parameter is only valid if bit 31 is set to "0" for both transmission
directions (subindex 1 and 2).
In the Lenze setting, SDO server channel 2 is deactivated (bit 31 = "1").
The identifier may only be changed when the SDO is invalid (bit 31 = "1").
[13-6] Data telegram assignment
How to change the identifier:
1. Deactivate identifier (set bit 31 to "1").
2. Change identifier.
3. Activate identifier (set bit 31 to "0").
Index:
I-1201
Name:
SDO2 server parameter
Subindex Default setting Setting range (min. value | unit | max. value) Access Data type
0: Highest subindex supported 3 - (read access only) ro U8
1: COB-ID client -> server (rx) 0x80000000 0 4294967295 rw U32
2: COB-ID server -> client (tx) 0x80000000 0 4294967295 rw U32
Subindex Meaning
1 Specification of the receive identifier
2 Specification of the transmit identifier
8th byte 7th byte 6th byte 5th byte
Data 4 Data 3 Data 2 Data 1
Bit 31 Bit 30 Bit 29 ... bit 11 Bit 10 ... bit 0
0/1 0 Extended identifier* 11-bit identifier
* The extended identifier is not supported - bit 11 ... bit 29 must be set to "0".
Bit Setting
Bit 31 0 SDO is valid.
1 SDO is invalid.