Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 205
5 Motor interface
5.8 Parameterisable additional functions
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8. Enter the maximum process current ("15 A") in C00022
.
9. Switch on the correction (C02859
= "ON").
When the correction of the stator leakage inductance is switched on, the same current
characteristic should occur, irrespective of the current magnitude.
Since the current controller gain is corrected actively, the step responses may differ slightly
compared to the previous measurements. In this case C00075
and C00076 must be optimised
one last time.
10. Save parameter set (C00002
= "11: Save start parameters").
Vista de página 204