13 Diagnostics & fault analysis
13.7 Error messages of the operating system
658
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Internal communication error (DMA) [0x007b0034]
Controller: Overload during acceleration phases [0x007b0035]
Internal communication error (MCTRL host) [0x007b0036]
PLC configuration invalid [0x007b0037]
Motor parameter identification was cancelled [0x007b0038]
Module ID (decimal) Error ID (decimal)
123: Motor control 52
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error. Please contact Lenze.
Module ID (decimal) Error ID (decimal)
123: Motor control 53
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Frequent or too long acceleration processes. Check drive dimensioning.
• Reduce steepness of acceleration ramps.
Module ID (decimal) Error ID (decimal)
123: Motor control 54
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error. Please contact Lenze.
Module ID (decimal) Error ID (decimal)
123: Motor control 55
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
An invalid control configuration has occurred. Load a different application.
Module ID (decimal) Error ID (decimal)
123: Motor control 56
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The motor current during identification was too high. The motor must not move during identification.
• Check motor parameters.