Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 831
14 Parameter reference
14.2 Parameter list | C00993
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00993
C00994
C00995
C00998
Parameter | Name:
C00993 | Flying restart: Integration time
Data type: UNSIGNED_32
Index: 23582
d
= 5C1E
h
From software version V3.0
Flying restart function
Setting range (min. value | unit | max. value) Lenze setting
1 ms 6000 60 ms
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00994 | Flying restart: Min. deviation
Data type: UNSIGNED_32
Index: 23581
d
= 5C1D
h
From software version V3.0
Flying restart function
Setting range (min. value | unit | max. value) Lenze setting
0.00 ° 90.00 5.00 °
Read access Write access CINH PLC STOP No transfer Scaling factor: 100
Parameter | Name:
C00995 | Flying restart: Delay time
Data type: UNSIGNED_32
Index: 23580
d
= 5C1C
h
From software version V3.0
Flying restart function
Setting range (min. value | unit | max. value) Lenze setting
0 ms 10000 0ms
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00998 | VFC: Frequency setpoint
Data type: INTEGER_32
Index: 23577
d
= 5C19
h
From software version V3.0
V/f control
Display range (min. value | unit | max. value)
-800.0 Hz 800.0
Read access Write access CINH PLC STOP No transfer Scaling factor: 10