Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 711
13 Diagnostics & fault analysis
13.7 Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Int. overflow C02647 (homing: Acceleration 2) [0x00b80032]
Int. overflow C02670 (positioner: Tol. for target position) [0x00b80033]
Cam data: Invalidated due to change of mechanical data [0x00b80034]
Module ID (decimal) Error ID (decimal)
184: Basic drive functions 50
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
From software version V3.0
Due to a subsequent change of the machine parameters
for gearbox ratio, feed constant, or resolution of an
encoder revolution, the value set in the parameter
cannot be displayed in the internal unit. See chapter
"Max. position, speed, and acceleration that can be
displayed internally".
• Check machine parameters and adapt them if
required.
• Change setting in C02647
.
Module ID (decimal) Error ID (decimal)
184: Basic drive functions 51
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
From software version V3.0
Due to a subsequent change of the machine parameters
for gearbox ratio, feed constant, or resolution of an
encoder revolution, the value set in the parameter
cannot be displayed in the internal unit. See chapter
"Max. position, speed, and acceleration that can be
displayed internally".
• Check machine parameters and adapt them if
required.
• Change setting in C02670
.
Module ID (decimal) Error ID (decimal)
184: Basic drive functions 52
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
From software version V4.0
One or several machine parameters have been changed
that have an influence on the internal scaling of the Cam
data. The Cam data has to be recalculated. See chapter
"Invalid Cam data due to changed machine parameters
".
Execute device command C00002
= "503: Calculate Cam
Data". This automatically resets the warning.