Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 637
13 Diagnostics & fault analysis
13.7 Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Runtime error [0x006a000d]
Application has stopped [0x006a000e]
Breakpoint reached [0x006a000f]
Faulty application parameter [0x006a0010]
Division by zero [0x006a0011]
Module ID (decimal) Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs 13
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
A runtime error has occurred in the application. The
application processing has been interrupted.
Remove runtime error in the application and retransfer
application to controller.
Module ID (decimal) Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs 14
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The application has been stopped using the device
command C00002
="32". All user tasks are stopped.
Restart application with device command C00002
="31".
Module ID (decimal) Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs 15
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The application has reached a set breakpoint and the
user task with the breakpoint has stopped.
Delete breakpoint and restart application.
Module ID (decimal) Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs 16
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
An invalid parameter description is available. Transmit application and parameter set to the controller
again.
Module ID (decimal) Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs 17
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
An impermissible division by zero occurred in the
application. The division has been intercepted and the
divisor was replaced by the value "1".
Replace application.